Mike Krzyzewski is really a famous coach of Dream Team. She has coached north america men's basketball team for some time, that's clinched numerous medals for his country. Following Londonfl jerseys supplyn Olympic was over, Krzyzewski told The Associated Press that this game will be his final one as national coach, a job he's held for seven years. He had left open the possibility of swomen nfl jerseystaying with the team beyond the London Games, when practice on Saturday said these will be his last Olympics.When asked if he was sure, Krzyzewski didn't hesitate before again saying, "yecheap nfl jerseys wholesales," this will be his last game "If we could win it, then it might be three major championships in a row, i always do not know when that has been done because we haven't usually won http://govoriotkrito.bg/libs/nflcn08.htmthe globe championships," Krzyzewski said. "It becomes an enormous thing for the program." Whatever, he's an awesome coach. His achievement are going to be remembered by the country.cheap nfl jerseys
你的位置:首页 > 新闻动态 > 技术动态

断路器的基本特性

2013/12/14 8:26:24      点击:
断路器的特性主要有:额定电压Ue;额定电流In;过载保护

(Ir或Irth)和短路保护(Im)的脱扣电流整定范围;额定短路分断电流(工业用断路器Icu;家用断路器Icn)等。
额定工作电压(Ue):这是断路器在正常(不间断的)的情况下工作的电压。
额定电流(In):这是配有专门的过电流脱扣继电器的断路器在制造厂家规定的环境温度下所能无限承受的最大电流值,不会超过电流承受部件规定的温度限值。
短路继电器脱扣电流整定值(Im):短路脱扣继电器(瞬时或短延时)用于高故障电流值出现时,使断路器快速跳闸,其跳闸极限Im。
额定短路分断能力(Icu或Icn):断路器的额定短路分断电流是断路器能够分断而不被损害的最高(预期的)电流值。标准中提供的电流值为故障电流交流分量的均方根值,计算标准值时直流暂态分量(总在最坏的情况短路下出现)假定为零。工业用断路器额定值(Icu)和家用断路器额定值(Icn)通常以kA均方根值的形式给出。
短路分断能力(Ics):断路器的额定分断能力分为额定极限短路分断能力和额定运行短路分断能力两种。

KBCPS(SKBO)控制保护断路器
国标《低压开关设备和控制设备低压断路器》(GB14048.2—94)对断路器额定极限短路分断能力和额定运行短路分断能力作了如下的解释:
1、断路器的额定极限短路分断能力:按规定的实验程序所规定的条件,不包括断路器继续承载其额定电流能力的分断能力;
2、断路器的额定运行短路分断能力:按规定的实验程序所规定的条件,包括断路器继续承载其额定电流能力的分断能力;
3、额定极限短路分断能力的试验程序为O—t—CO。
其具体试验是:把线路的电流调整到预期的短路电流值(例如380V ,50kA),而试验按钮未合,被试断路器处于合闸位置,按下试验按钮,断路器通过50kA短路电流,断路器立即开断(open简称O),断路器应完好,且能再合闸。t为间歇时间,一般为3min,此时线路仍处于热备状态,断路器再进行一次接通(close简称C)和紧接着的开断(O),(接通试验是考核断路器在峰值电流下的电动和热稳定性)。此程序即为CO。断路器能完全分断,则其极限短路分断能力合格。
4、断路器的额定运行短路分断能力(Icn)的试验程序为O—t—CO—t—CO。它比Icn的试验程序多了一次CO,经过试验,断路器能完全分断、熄灭电弧,就认定它的额定运行短路分断能力合格。
因此,可以看出,额定极限短路分断能力Icn指的是低压断路器在分断了断路器出线端最大三相短路电流后还可再正常运行并再分断这一短路电流一次,至于以后是否能正常接通及分断,断路器不予以保证;而额定运行短路分断能力Ics指的是断路器在其出线端最大三相短路电流发生时可多次正常分断。
IEC947—2《低压开关设备和控制设备低压断路器》标准规定:A类断路器(指仅有过载长延时、

短路瞬动的断路器)的Ics可以是25%、50%、75%和100%。B类断路器(有过载长延时、短路短延时、短路瞬动的三段保护的断路器)的Ics可以是Ics的50%、75%和100%。因此可以看出,额定运行短路分断能力是一种比额定极限短路分断电流小的分断电流值,Ics是Icu的一个百分数。
一般来说,具有过载长延时、短路短延时和短路瞬动三段保护功能的断路器,能实现选择性保护,大多数主干线(包括变压器的出线端)都采用它作主保护开关。不具备短路短延时功能的断路器(仅有过载长延时和短路瞬动二段保护),不能作选择性保护,它们只能使用于支路。IEC92《船舶电气》指出:具有三段保护的断路器,偏重于它的运行短路分断能力值,而使用于分支线路的断路器,应确保它有足够的极限短路分断能力值。
无论是哪种断路器,虽然都具备Icu和Ics这两个重要的技术指标。

但是,作为支线上使用的断路器,可以仅满足额定极限短路分断能力即可。较普遍的偏颇是宁取大,不取正合适,认为取大保险。但取得过大,会造成不必要的浪费(同类型断路器,其H型—高分断型,比S型—普通型的价格要贵1.3倍~1.8倍)。因此支线上的断路器没有必要一味追求它的运行短路分断能力指标。而对于干线上使用的断路器,不仅要满足额定极限短路分断能力的要求,同时也应该满足额定运行短路分断能力的要求,如果仅以额定极限短路分断能力Icu来衡量其分断能力合格与否,将会给用户带来不安全的隐患。
断路器是一种基本的低压电器,断路器具有过载、短路和欠电压保护功能,有保护线路和电源的能力。
主要技术指标是额定电压、额定电流。断路器根据不同的应用具有不同的功能,品种、规格很多,具体的技术指标也很多。
断路器自由脱扣:断路器在合闸过程中的任何时刻,若是保护动作接通跳闸回路,断路器完全能可靠地断开,这就叫自由脱扣。带有自由脱扣的断路器,可以保证断路器合闸短路故障时,能迅速断开,可以避免扩大事故的范围。